Call Now Book Service Online Estimate Specials

Christopher

Christopher

Service Technician

Rating

Reviews

Christopher has been part of the Hydes team since 2022, bringing both technical expertise and a personable approach to every service call. Customers often praise him for being thorough, professional, and willing to take the time to explain his work and answer questions. Known for his reliability and friendly manner, Christopher makes sure each visit leaves customers confident and comfortable with their systems. Christopher is NATE certified, a distinction regarded as the highest standard in HVAC. Outside of work, he enjoys spending time with his wife Sylvia and their two children, as well as singing, baking, and attending church. An avid listener of bossa nova music, he especially enjoys artists such as Antonio Carlos Jobim, João Gilberto, and Rosinha de Valença.

Name: Christopher

Certifications: NATE

Recent Jobs and Reviews

Rated 4.9 out of 5 stars based on 1348 customer reviews

Customers say: The overall sentiment across these reviews is overwhelmingly positive, reflecting high levels of customer satisfaction and appreciation for the service provided. Customers consistently express gratitude and praise for the professionalism, knowledge, and courtesy demonstrated by the technicians. Recurring themes include exceptional customer service, with technicians being described as friendly, respectful, polite, and professional throughout their interactions. Technical expertise is another dominant positive trend, as customers frequently commend the thorough diagnostics, efficient problem-solving, and clear explanations provided during service calls. Many reviewers highlight the promptness and reliability of the service, noting quick response times, punctuality, and efficient completion of work. The dedication to resolving complex or frustrating situations is particularly appreciated, with several customers expressing relief and happiness at having their HVAC and electrical issues successfully addressed. There is also notable appreciation for the transparency and honesty in service delivery, with customers valuing straightforward communication without unnecessary upselling. Long-term customer loyalty emerges as a theme, with multiple reviewers mentioning years of positive experiences and enthusiastic recommendations to neighbors and friends. The overall tone is one of trust, satisfaction, and genuine appreciation for quality workmanship and customer-focused service.

At a glance

Hydes Air Conditioning has completed 25 jobs in September 2026.

The 15 customer reviews shown here average 5.0 out of 5.

The most recent job was on September 17, 2026.

Recent work covers Palm Desert, CA, Indio, CA, Palm Springs, CA, Indian Wells, CA and Cathedral City, CA.

Reviews

Excellent service great communication
Allan - Cathedral City, CA 92234
Excellent Service. Christopher has serviced our home many times. Knows our home and units here. He is very knowledgeable and has great customer ser
Christopher arrived on time. Performed service and communicated what he was going to do and gave update after
Jim - Indio, CA 92203
Easy service
Kerry - Indio, CA 92203
Seasonal Maintenance
On time, let us know he was on his way, explained what he did and was efficient.
Vincent - Indio, CA 92203
Excellent service
Chris was very thorough, very personable and informative
Keith - Palm Desert, CA 92211
Great Heating Service
Chris from Hydes notified us of his arrival time and performed the maintenance interval on our furnace. He reported the system checks and the results all satisfactory. Always pleased with Chris's profesdionalism.
Ed - Indio, CA 92203
Great service
All good.
Bill - Palm Springs, CA 92264
Always excellent
They are very responsive, their service techs are knowledgeable and clean (booties). Efficiency at its best!
Tammy - Indian Wells, CA 92210
Excellent
Mike - Palm Desert, CA 92211
Efficient
Donna - Palm Desert, CA 92260
Great Service
Christopher was so warm, kind & professional. He performed a service call for maintenance. Changed the filter and checked the overall performance of my system interior and exterior unit, answered a couple things I needed clarity on, gave me couple suggestions, and was on his way. No trying to upsell me on anything, he just said the report will be send email. I would never trust anybody else but Hydes!
Carole - Palm Desert, CA 92260
Really appreciate the great service!
We like having Hyde’s proactive service to keep our systems running well.
David - Palm Springs, CA 92264
Great!
Very nice and helpful.
Ester - Palm Desert, CA 92211
Timely and good service in very hot attic setting.
Steve - Palm Desert, CA 92211
Excellent Service. Very personable
Nancy - Palm Desert, CA 92211

Job Locations

Christopher J.
Christopher J.
Estimates sent via email
Desert Hot Springs, CA 92240
Christopher J.
Christopher J.
Performed a maintenance and safety check on the indoor unit. Checked static pressure and blower motor amp draw. ECM blower motor. Cycled system in heating. Informed client that system only runs for a few minutes due to an open safety switch. Checked temperature heat rise. No carbon monoxide was detected in the home. Pre-booked outdoor unit maintenance and safety check.
Palm Desert, CA 92260
Palm Desert, CA - Performed a maintenance and safety check on the indoor unit. Checked static pressure and blower motor amp draw. ECM blower motor. Cycled system in heating. Informed client that system only runs for a few minutes due to an open safety switch. Checked temperature heat rise. No carbon monoxide was detected in the home. Pre-booked outdoor unit maintenance and safety check.
Palm Desert, CA - Performed a maintenance and safety check on the indoor unit. Checked static pressure and blower motor amp draw. ECM blower motor. Cycled system in heating. Informed client that system only runs for a few minutes due to an open safety switch. Checked temperature heat rise. No carbon monoxide was detected in the home. Pre-booked outdoor unit maintenance and safety check.
Christopher J.
Christopher J.
Performed a safety and maintenance service on indoor unit. Cycle system in heating. Replaced filter, cleared condensate and no carbon monoxide was detected in the home. Checked blower motor amp draw and static pressure measurements. Estimate sent for float safety switch via email. System is functioning according to manufacture specifications. Pre-booked outdoor unit maintenance and safety inspection.
Palm Desert, CA 92260
Palm Desert, CA - Performed a safety and maintenance service on indoor unit. Cycle system in heating. Replaced filter, cleared condensate and no carbon monoxide was detected in the home. Checked blower motor amp draw and static pressure measurements. Estimate sent for float safety switch via email. System is functioning according to manufacture specifications. Pre-booked outdoor unit maintenance and safety inspection.
Palm Desert, CA - Performed a safety and maintenance service on indoor unit. Cycle system in heating. Replaced filter, cleared condensate and no carbon monoxide was detected in the home. Checked blower motor amp draw and static pressure measurements. Estimate sent for float safety switch via email. System is functioning according to manufacture specifications. Pre-booked outdoor unit maintenance and safety inspection.
Christopher J.
Christopher J.
Client dealing with excessive dust issues in the home. Ductwork is original to the home and over 20 years of age. Diagnosed excessive dust in blower housing/wheel, as well as evaporator coil. Client is interested in a quote for blow-in insulation, complete duct replacement as well as evaporator/blower wheel and housing cleaning. House is 1700 ft.². Will be in communication with Barry for quotes.
Desert Hot Springs, CA 92240
Christopher J.
Christopher J.
Performed an indoor maintenance and safety check. Upon arrival, client stated that furnace would make a whistling noise during the sequence of operation. Cycled system in heating and system did not whistle or make excessive noise. Checked temperature heat rise - no carbon monoxide was detected in the home. Measured static pressure measurements and electric motor readings. ECM blower motor. Installed new P-trap and cleanout for primary drain line – paid via C. C. Pre-booked outdoor maintenance and safety check. System is servicing the home at the time of service.
Cathedral City, CA 92234
Cathedral City, CA - Performed an indoor maintenance and safety check. Upon arrival, client stated that furnace would make a whistling noise during the sequence of operation. Cycled system in heating and system did not whistle or make excessive noise. Checked temperature heat rise - no carbon monoxide was detected in the home. Measured static pressure measurements and electric motor readings. ECM blower motor. Installed new P-trap and cleanout for primary drain line – paid via C. C. Pre-booked outdoor maintenance and safety check. System is servicing the home at the time of service.
Cathedral City, CA - Performed an indoor maintenance and safety check. Upon arrival, client stated that furnace would make a whistling noise during the sequence of operation. Cycled system in heating and system did not whistle or make excessive noise. Checked temperature heat rise - no carbon monoxide was detected in the home. Measured static pressure measurements and electric motor readings. ECM blower motor. Installed new P-trap and cleanout for primary drain line – paid via C. C. Pre-booked outdoor maintenance and safety check. System is servicing the home at the time of service.
Christopher J.
Christopher J.
Performed an indoor maintenance and safety inspection. Gas furnace is located in an outdoor mechanical closet. Checked electric motors. Static pressure: N/A. Equipment executed the sequence of operation in heating. Temperature heat rise. Perform service on garage mini split. HVAC duct inspection. System is currently functioning according to manufacture specifications. Pre-booked heating maintenance.
Coachella, CA 92236
Coachella, CA - Performed an indoor maintenance and safety inspection. Gas furnace is located in an outdoor mechanical closet. Checked electric motors. Static pressure: N/A. Equipment executed the sequence of operation in heating. Temperature heat rise. Perform service on garage mini split. HVAC duct inspection. System is currently functioning according to manufacture specifications. Pre-booked heating maintenance.
Coachella, CA - Performed an indoor maintenance and safety inspection. Gas furnace is located in an outdoor mechanical closet. Checked electric motors. Static pressure: N/A. Equipment executed the sequence of operation in heating. Temperature heat rise. Perform service on garage mini split. HVAC duct inspection. System is currently functioning according to manufacture specifications. Pre-booked heating maintenance.
Christopher J.
Christopher J.
Performed an indoor maintenance and safety check on two split systems. Gas furnace executed the sequence of operation in heating. No carbon monoxide was detected in the home. Checked electric motors, capacitors and static pressure measurements. Excellent temperature heat rise. Heat pump: performed a refrigerant circuit diagnostic, blower motor amp draw and static pressure measurements. Replaced filters, cleared condensate and cleaned mechanical platform of dirt and debris. Installed Jones valve on gas furnace – paid via CC. Both systems are functioning according to manufacture specifications.
Indio, CA 92203
Indio, CA - Performed an indoor maintenance and safety check on two split systems. Gas furnace executed the sequence of operation in heating. No carbon monoxide was detected in the home. Checked electric motors, capacitors and static pressure measurements. Excellent temperature heat rise.

Heat pump: performed a refrigerant circuit diagnostic, blower motor amp draw and static pressure measurements. Replaced filters, cleared condensate and cleaned mechanical platform of dirt and debris. Installed Jones valve on gas furnace – paid via CC. Both systems are functioning according to manufacture specifications.
Indio, CA - Performed an indoor maintenance and safety check on two split systems. Gas furnace executed the sequence of operation in heating. No carbon monoxide was detected in the home. Checked electric motors, capacitors and static pressure measurements. Excellent temperature heat rise.

Heat pump: performed a refrigerant circuit diagnostic, blower motor amp draw and static pressure measurements. Replaced filters, cleared condensate and cleaned mechanical platform of dirt and debris. Installed Jones valve on gas furnace – paid via CC. Both systems are functioning according to manufacture specifications.
Christopher J.
Christopher J.
Performed an indoor maintenance and safety check on a split system. Cleared condensate drain and thoroughly cleaned mechanical platform of dirt and debris. Recommend installing a condensate Jones valve on primary line, to ensure proper clearing of P-trap – estimate sent via email. Measured blower capacitor, blower motor amp draw and static pressure readings. Evap coil: clean. Excellent temperature heat rise with no carbon monoxide detected in the home. Equipment executed the sequence of operation in heating. Pre-booked cooling maintenance. System is heating the home at the time of maintenance and inspection.
Indio, CA 92203
Indio, CA - Performed an indoor maintenance and safety check on a split system. Cleared condensate drain and thoroughly cleaned mechanical platform of dirt and debris. Recommend installing a condensate Jones valve on primary line, to ensure proper clearing of P-trap – estimate sent via email. Measured blower capacitor, blower motor amp draw and static pressure readings. Evap coil: clean. Excellent temperature heat rise with no carbon monoxide detected in the home. Equipment executed the sequence of operation in heating. Pre-booked cooling maintenance. System is heating the home at the time of maintenance and inspection.
Indio, CA - Performed an indoor maintenance and safety check on a split system. Cleared condensate drain and thoroughly cleaned mechanical platform of dirt and debris. Recommend installing a condensate Jones valve on primary line, to ensure proper clearing of P-trap – estimate sent via email. Measured blower capacitor, blower motor amp draw and static pressure readings. Evap coil: clean. Excellent temperature heat rise with no carbon monoxide detected in the home. Equipment executed the sequence of operation in heating. Pre-booked cooling maintenance. System is heating the home at the time of maintenance and inspection.
Christopher J.
Christopher J.
Performed a cooling maintenance on two micro-channel, straight cool condensers. Found outdoor units full of dirt and debris. Washed units from the inside out. Client replaced filters previously. Disconnect boxes are old, sun damaged and extremely tight. Service technicians are not able to use them, due to a high possibility of damaging boxes. Checked dual run capacitor, electric motors and refrigerant circuit diagnostics. Thermostats: good. Systems are currently cooling the home at the time of maintenance. Clients to book heating maintenance in the winter. Enrolled in club membership – paid via check.
Palm Desert, CA 92211
Palm Desert, CA - Performed a cooling maintenance on two micro-channel, straight cool condensers. Found outdoor units full of dirt and debris. Washed units from the inside out. Client replaced filters previously. Disconnect boxes are old, sun damaged and extremely tight. Service technicians are not able to use them, due to a high possibility of damaging boxes. Checked dual run capacitor, electric motors and refrigerant circuit diagnostics. Thermostats: good. Systems are currently cooling the home at the time of maintenance. Clients to book heating maintenance in the winter. Enrolled in club membership – paid via check.
Palm Desert, CA - Performed a cooling maintenance on two micro-channel, straight cool condensers. Found outdoor units full of dirt and debris. Washed units from the inside out. Client replaced filters previously. Disconnect boxes are old, sun damaged and extremely tight. Service technicians are not able to use them, due to a high possibility of damaging boxes. Checked dual run capacitor, electric motors and refrigerant circuit diagnostics. Thermostats: good. Systems are currently cooling the home at the time of maintenance. Clients to book heating maintenance in the winter. Enrolled in club membership – paid via check.
Christopher J.
Christopher J.
Performed a heating maintenance on a platinum system. Checked refrigerant circuit diagnostic, static pressure and blower motor amp draw readings. Cleared condensate drain line from the attic and cleaned Accu clean air filter with CO2 tank. System performed according to manufacture specifications. Pre-booked cooling maintenance for the month of April.
Palm Desert, CA 92211
Palm Desert, CA - Performed a heating maintenance on a platinum system. Checked refrigerant circuit diagnostic, static pressure and blower motor amp draw readings. Cleared condensate drain line from the attic and cleaned Accu clean air filter with CO2 tank. System performed according to manufacture specifications. Pre-booked cooling maintenance for the month of April.
Palm Desert, CA - Performed a heating maintenance on a platinum system. Checked refrigerant circuit diagnostic, static pressure and blower motor amp draw readings. Cleared condensate drain line from the attic and cleaned Accu clean air filter with CO2 tank. System performed according to manufacture specifications. Pre-booked cooling maintenance for the month of April.
Christopher J.
Christopher J.
Estimate to replace existing Daikin garage ductless with a AS Mitsubishi ductless heat pump. Add surge protection to all 3 systems, install Honeywell WiFi thermostat to casita and reduce fan speed in casita air handler. HVAC technician: installed Honeywell S200, linking Wi-Fi and client cell phone to thermostat. Reduced casita CFM to 350. Installed surge protectors at garage POV, disconnect for mini split/Casita heat pump and main condenser. Installers to collect for service.
Palm Desert, CA 92211
Christopher J.
Christopher J.
Demand call: thermostat error code During service, replaced defective float safety switch on platinum system. Tested and cleared primary drain line – courtesy. Repair under warranty. Error code on ECOBEE thermostat stated system had shut down on two consecutive days, stating there may be a problem with HVAC system, due to excessive temperature heat rise inside of the home. This is symptomatic of an outdoor unit that has powered down. Charged older system with 1 pound of refrigerant and double checked my previous electrical readings – capacitors, running compressor amp draw, starting compressor amp draw. Also measured a 30° temperature split (above coil/blower housing). I believe, theoretically, that the system has shut down due to compressor thermal overload. Educated clients concerning the cause and reassured them the issue should not arise again due to lower ambient temperatures. Charged clients credit card on file for refrigerant. Both systems are cooling the home at the time of s
Indian Wells, CA 92210
Indian Wells, CA - Demand call: thermostat error code

During service, replaced defective float safety switch on platinum system. Tested and cleared primary drain line – courtesy. Repair under warranty.

Error code on ECOBEE thermostat stated system had shut down on two consecutive days, stating there may be a problem with HVAC system, due to excessive temperature heat rise inside of the home. This is symptomatic of an outdoor unit that has powered down. Charged older system with 1 pound of refrigerant and double checked my previous electrical readings – capacitors, running compressor amp draw, starting compressor amp draw. Also measured a 30° temperature split (above coil/blower housing). I believe, theoretically, that the system has shut down due to compressor thermal overload. Educated clients concerning the cause and reassured them the issue should not arise again due to lower ambient temperatures. Charged clients credit card on file for refrigerant. Both systems are cooling the home at the time of s
Indian Wells, CA - Demand call: thermostat error code

During service, replaced defective float safety switch on platinum system. Tested and cleared primary drain line – courtesy. Repair under warranty.

Error code on ECOBEE thermostat stated system had shut down on two consecutive days, stating there may be a problem with HVAC system, due to excessive temperature heat rise inside of the home. This is symptomatic of an outdoor unit that has powered down. Charged older system with 1 pound of refrigerant and double checked my previous electrical readings – capacitors, running compressor amp draw, starting compressor amp draw. Also measured a 30° temperature split (above coil/blower housing). I believe, theoretically, that the system has shut down due to compressor thermal overload. Educated clients concerning the cause and reassured them the issue should not arise again due to lower ambient temperatures. Charged clients credit card on file for refrigerant. Both systems are cooling the home at the time of s
Christopher J.
Christopher J.
Performed a heating maintenance on an 80% efficiency gas furnace, located in the attic. Cleared condensate with CO2 tank and condensate brush. Replaced filter. Equipment executed the sequence of operation in heating. Check capacitor, blower motor amp draw and static pressure measurements. No carbon monoxide was detected in the home. System is functioning according to manufacturer specifications. Pre-booked cooling maintenance.
Indio, CA 92203
Indio, CA - Performed a heating maintenance on an 80% efficiency gas furnace, located in the attic. Cleared condensate with CO2 tank and condensate brush. Replaced filter. Equipment executed the sequence of operation in heating. Check capacitor, blower motor amp draw and static pressure measurements. No carbon monoxide was detected in the home. System is functioning according to manufacturer specifications. Pre-booked cooling maintenance.
Indio, CA - Performed a heating maintenance on an 80% efficiency gas furnace, located in the attic. Cleared condensate with CO2 tank and condensate brush. Replaced filter. Equipment executed the sequence of operation in heating. Check capacitor, blower motor amp draw and static pressure measurements. No carbon monoxide was detected in the home. System is functioning according to manufacturer specifications. Pre-booked cooling maintenance.
Christopher J.
Christopher J.
Performed a heating maintenance on a casita heat pump and a gas furnace, located in the attic – master closet access. Measured static pressure measurements and blower motor amp draw. Replaced blower motor capacitor – paid via CC. Cleared condensate drain line. Gas furnace executed the sequence of operation in heating. Heat pump refrigerant circuit diagnostics was good and cycled system in heating. Excellent temperature heat rise from gas furnace. Both systems are functioning according to manufacture specifications. Pre-booked cooling maintenance.
Indio, CA 92203
Indio, CA - Performed a heating maintenance on a casita heat pump and a gas furnace, located in the attic – master closet access. Measured static pressure measurements and blower motor amp draw. Replaced blower motor capacitor – paid via CC. Cleared condensate drain line. Gas furnace executed the sequence of operation in heating. Heat pump refrigerant circuit diagnostics was good and cycled system in heating. Excellent temperature heat rise from gas furnace. Both systems are functioning according to manufacture specifications. Pre-booked cooling maintenance.
Indio, CA - Performed a heating maintenance on a casita heat pump and a gas furnace, located in the attic – master closet access. Measured static pressure measurements and blower motor amp draw. Replaced blower motor capacitor – paid via CC. Cleared condensate drain line. Gas furnace executed the sequence of operation in heating. Heat pump refrigerant circuit diagnostics was good and cycled system in heating. Excellent temperature heat rise from gas furnace. Both systems are functioning according to manufacture specifications. Pre-booked cooling maintenance.
Christopher J.
Christopher J.
Performed a heating maintenance on a gas furnace, located in the attic. Client replaced filter. Cleared condensate drain line from external termination. Equipment executed the sequence of operation in heating with no carbon monoxide detected during service. Checked blower motor amp draw and static pressure measurements. ECM blower motor. System is heating the home at the time of maintenance. Pre-booked cooling maintenance.
Indio, CA 92203
Indio, CA - Performed a heating maintenance on a gas furnace, located in the attic. Client replaced filter. Cleared condensate drain line from external termination. Equipment executed the sequence of operation in heating with no carbon monoxide detected during service. Checked blower motor amp draw and static pressure measurements. ECM blower motor. System is heating the home at the time of maintenance. Pre-booked cooling maintenance.
Indio, CA - Performed a heating maintenance on a gas furnace, located in the attic. Client replaced filter. Cleared condensate drain line from external termination. Equipment executed the sequence of operation in heating with no carbon monoxide detected during service. Checked blower motor amp draw and static pressure measurements. ECM blower motor. System is heating the home at the time of maintenance. Pre-booked cooling maintenance.
Christopher J.
Christopher J.
Performed a cooling maintenance on a package heat pump. Washed outdoor unit and replaced filter (no ladder needed). Check the electric motors, capacitors and refrigerant circuit diagnostics. Disconnect/thermostat: good. Pre-booked heating maintenance. System is cooling the home at the time of maintenance.
Palm Springs, CA 92264
Palm Springs, CA - Performed a cooling maintenance on a package heat pump. Washed outdoor unit and replaced filter (no ladder needed). Check the electric motors, capacitors and refrigerant circuit diagnostics. Disconnect/thermostat: good. Pre-booked heating maintenance. System is cooling the home at the time of maintenance.
Palm Springs, CA - Performed a cooling maintenance on a package heat pump. Washed outdoor unit and replaced filter (no ladder needed). Check the electric motors, capacitors and refrigerant circuit diagnostics. Disconnect/thermostat: good. Pre-booked heating maintenance. System is cooling the home at the time of maintenance.
Christopher J.
Christopher J.
Performed a cooling maintenance on two split TRANE units. Cleared condensate drain, washed outdoor unit and replace filters. Installed two float safety switch – paid via CC. Checked capacitors, electric motors and refrigerant circuit diagnostics. Thermostat/disconnect box: good. Both systems are cooling the home at the time of maintenance.
Palm Springs, CA 92262
Palm Springs, CA - Performed a cooling maintenance on two split TRANE units. Cleared condensate drain, washed outdoor unit and replace filters. Installed two float safety switch – paid via CC. Checked capacitors, electric motors and refrigerant circuit diagnostics. Thermostat/disconnect box: good. Both systems are cooling the home at the time of maintenance.
Palm Springs, CA - Performed a cooling maintenance on two split TRANE units. Cleared condensate drain, washed outdoor unit and replace filters. Installed two float safety switch – paid via CC. Checked capacitors, electric motors and refrigerant circuit diagnostics. Thermostat/disconnect box: good. Both systems are cooling the home at the time of maintenance.
Christopher J.
Christopher J.
Performed a cooling maintenance on a partial system recent install. Upon arrival, secondary drain was dripping water. Access Jones valve and cleared primary condensate from the attic. Replaced filter. Refrigerant circuit diagnostic: delta T and temperature/pressure readings. Checked capacitors and electrical motor amp draw readings. Thermostat/disconnect: good. Pre-booked heating maintenance. System is cooling the home at the time of maintenance.
Palm Desert, CA 92211
Palm Desert, CA - Performed a cooling maintenance on a partial system recent install. Upon arrival, secondary drain was dripping water. Access Jones valve and cleared primary condensate from the attic. Replaced filter. Refrigerant circuit diagnostic: delta T and temperature/pressure readings. Checked capacitors and electrical motor amp draw readings. Thermostat/disconnect: good. Pre-booked heating maintenance. System is cooling the home at the time of maintenance.
Palm Desert, CA - Performed a cooling maintenance on a partial system recent install. Upon arrival, secondary drain was dripping water. Access Jones valve and cleared primary condensate from the attic. Replaced filter. Refrigerant circuit diagnostic: delta T and temperature/pressure readings. Checked capacitors and electrical motor amp draw readings. Thermostat/disconnect: good. Pre-booked heating maintenance. System is cooling the home at the time of maintenance.
Christopher J.
Christopher J.
Perform a cooling maintenance on a split system. Replaced filter and cleared compensate. Checked refrigerant circuit diagnostic, electric motors and capacitors. System is functioning according to manufacture specifications. Pre-booked heating maintenance.
Palm Desert, CA 92211
Palm Desert, CA - Perform a cooling maintenance on a split system. Replaced filter and cleared compensate. Checked refrigerant circuit diagnostic, electric motors and capacitors. System is functioning according to manufacture specifications. Pre-booked heating maintenance.
Christopher J.
Christopher J.
Performed a cooling maintenance on a split platinum and American Standard, 5-ton split system. Diagnosed a defective float safety switch on platinum system. Need to return at a later date to replace under warranty. 5 ton, 2017 system was low on refrigerant according to temperature and pressure readings. Estimate sent to recharge system – may take anywhere from 1 to 3 pounds. Checked electrical motors and running/starting capacitors. Washed outdoor units, replaced filters and cleared condensate. Both systems are currently cooling the home at the time of maintenance.
Indian Wells, CA 92210
Indian Wells, CA - Performed a cooling maintenance on a split platinum and American Standard, 5-ton split system. Diagnosed a defective float safety switch on platinum system. Need to return at a later date to replace under warranty. 5 ton, 2017 system was low on refrigerant according to temperature and pressure readings. Estimate sent to recharge system – may take anywhere from 1 to 3 pounds. Checked electrical motors and running/starting capacitors. Washed outdoor units, replaced filters and cleared condensate. Both systems are currently cooling the home at the time of maintenance.
Indian Wells, CA - Performed a cooling maintenance on a split platinum and American Standard, 5-ton split system. Diagnosed a defective float safety switch on platinum system. Need to return at a later date to replace under warranty. 5 ton, 2017 system was low on refrigerant according to temperature and pressure readings. Estimate sent to recharge system – may take anywhere from 1 to 3 pounds. Checked electrical motors and running/starting capacitors. Washed outdoor units, replaced filters and cleared condensate. Both systems are currently cooling the home at the time of maintenance.
Christopher J.
Christopher J.
Performed a heating maintenance on an 80% efficiency gas furnace. Checked static pressure, blower motor amp draw and heat rise. Equipment executed the sequence of operation in heating. Changed blower capacitor due to capacitance measuring outside of manufacturer specifications – paid via CC. System is functioning according to manufacture specifications.
Palm Desert, CA 92211
Palm Desert, CA - Performed a heating maintenance on an 80% efficiency gas furnace. Checked static pressure, blower motor amp draw and heat rise. Equipment executed the sequence of operation in heating. Changed blower capacitor due to capacitance measuring outside of manufacturer specifications – paid via CC. System is functioning according to manufacture specifications.
Palm Desert, CA - Performed a heating maintenance on an 80% efficiency gas furnace. Checked static pressure, blower motor amp draw and heat rise. Equipment executed the sequence of operation in heating. Changed blower capacitor due to capacitance measuring outside of manufacturer specifications – paid via CC. System is functioning according to manufacture specifications.
Christopher J.
Christopher J.
Performed a cooling maintenance on a split system with micro channel condenser coil. Refrigerant circuit diagnostics checked out good. Checked running/starting amperage on compressor/fan motor and measured running/starting capacitors. Washed outdoor units and performed courtesy service on mini splits. Thermostat/disconnect box: good. Pre-booked heating maintenance. System is cooling the home at the time of maintenance.
Palm Desert, CA 92260
Palm Desert, CA - Performed a cooling maintenance on a split system with micro channel condenser coil. Refrigerant circuit diagnostics checked out good. Checked running/starting amperage on compressor/fan motor and measured running/starting capacitors. Washed outdoor units and performed courtesy service on mini splits. Thermostat/disconnect box: good. Pre-booked heating maintenance. System is cooling the home at the time of maintenance.
Palm Desert, CA - Performed a cooling maintenance on a split system with micro channel condenser coil. Refrigerant circuit diagnostics checked out good. Checked running/starting amperage on compressor/fan motor and measured running/starting capacitors. Washed outdoor units and performed courtesy service on mini splits. Thermostat/disconnect box: good. Pre-booked heating maintenance. System is cooling the home at the time of maintenance.
Christopher J.
Christopher J.
Performed a cooling maintenance on a split system. Surge protection: operative. Checked electric motors, capacitors and refrigerant circuit diagnostics. Washed outdoor unit and replaced filter. Thermostat: good. Service panel serves as outdoor disconnect. System is cooling the home at the time of maintenance.
Palm Desert, CA 92260
Palm Desert, CA - Performed a cooling maintenance on a split system. Surge protection: operative. Checked electric motors, capacitors and refrigerant circuit diagnostics. Washed outdoor unit and replaced filter. Thermostat: good. Service panel serves as outdoor disconnect. System is cooling the home at the time of maintenance.
Christopher J.
Christopher J.
Performed a heating maintenance on three gas up-flows, located in two outdoor mechanical closets and one mechanical closet in the laundry room. Installed Jones valve/float safety switch at bedroom and living room units – paid via C. C. Checked blower motor amp draw and capacitors. Measured static pressure and temperature heat rise. All three gas furnaces executed the sequence of operation in heating. Replaced filters and cleared condensate drain drains. All three systems are functional in heating at the time of maintenance.
Palm Desert, CA 92260
Palm Desert, CA - Performed a heating maintenance on three gas up-flows, located in two outdoor mechanical closets and one mechanical closet in the laundry room. Installed Jones valve/float safety switch at bedroom and living room units – paid via C. C. Checked blower motor amp draw and capacitors. Measured static pressure and temperature heat rise. All three gas furnaces executed the sequence of operation in heating. Replaced filters and cleared condensate drain drains. All three systems are functional in heating at the time of maintenance.
Palm Desert, CA - Performed a heating maintenance on three gas up-flows, located in two outdoor mechanical closets and one mechanical closet in the laundry room. Installed Jones valve/float safety switch at bedroom and living room units – paid via C. C. Checked blower motor amp draw and capacitors. Measured static pressure and temperature heat rise. All three gas furnaces executed the sequence of operation in heating. Replaced filters and cleared condensate drain drains. All three systems are functional in heating at the time of maintenance.
Christopher J.
Christopher J.
Performed a cooling maintenance on a split Amana. Cleared condensate, replace filter and washed outdoor unit. Checked capacitor, starting/running amperage on all motors and performed a refrigerant circuit diagnostic. Delta T was good with home cooled to 72°. Tested thermostat for calibration and accuracy. Disconnect box: good. System is cooling the home at the time of maintenance.
Palm Desert, CA 92260
Palm Desert, CA - Performed a cooling maintenance on a split Amana. Cleared condensate, replace filter and washed outdoor unit. Checked capacitor, starting/running amperage on all motors and performed a refrigerant circuit diagnostic. Delta T was good with home cooled to 72°. Tested thermostat for calibration and accuracy. Disconnect box: good. System is cooling the home at the time of maintenance.
Palm Desert, CA - Performed a cooling maintenance on a split Amana. Cleared condensate, replace filter and washed outdoor unit. Checked capacitor, starting/running amperage on all motors and performed a refrigerant circuit diagnostic. Delta T was good with home cooled to 72°. Tested thermostat for calibration and accuracy. Disconnect box: good. System is cooling the home at the time of maintenance.