Call Now Book Service Online Estimate Specials

Christopher

Christopher

Service Technician

Rating

Reviews

Christopher has been part of the Hydes team since 2022, bringing both technical expertise and a personable approach to every service call. Customers often praise him for being thorough, professional, and willing to take the time to explain his work and answer questions. Known for his reliability and friendly manner, Christopher makes sure each visit leaves customers confident and comfortable with their systems. Christopher is NATE certified, a distinction regarded as the highest standard in HVAC. Outside of work, he enjoys spending time with his wife Sylvia and their two children, as well as singing, baking, and attending church. An avid listener of bossa nova music, he especially enjoys artists such as Antonio Carlos Jobim, João Gilberto, and Rosinha de Valença.

Name: Christopher

Certifications: NATE

Recent Jobs and Reviews

Rated 4.9 out of 5 stars based on 1357 customer reviews

Customers say: The overall sentiment across these reviews is overwhelmingly positive, reflecting high levels of customer satisfaction and appreciation for the service provided. Customers consistently express gratitude and praise for the professionalism, knowledge, and courtesy demonstrated by the technicians. Recurring themes include exceptional customer service, with technicians being described as friendly, respectful, polite, and professional throughout their interactions. Technical expertise is another dominant positive trend, as customers frequently commend the thorough diagnostics, efficient problem-solving, and clear explanations provided during service calls. Many reviewers highlight the promptness and reliability of the service, noting quick response times, punctuality, and efficient completion of work. The dedication to resolving complex or frustrating situations is particularly appreciated, with several customers expressing relief and happiness at having their HVAC and electrical issues successfully addressed. There is also notable appreciation for the transparency and honesty in service delivery, with customers valuing straightforward communication without unnecessary upselling. Long-term customer loyalty emerges as a theme, with multiple reviewers mentioning years of positive experiences and enthusiastic recommendations to neighbors and friends. The overall tone is one of trust, satisfaction, and genuine appreciation for quality workmanship and customer-focused service.

At a glance

Hydes Air Conditioning has completed 25 jobs between September 2026 and October 2026.

The 15 customer reviews shown here average 5.0 out of 5.

The most recent job was on October 2, 2026.

Recent work covers La Quinta, CA, Indio, CA, Palm Desert, CA, Rancho Mirage, CA and Palm Springs, CA.

Reviews

Outstanding!
Christopher did an amazing job. He was friendly, professional and made the whole experience as good as possible. He went above and beyond to make us comfortable with the entire process. He is an employee who makes your company look really good! Thanks!
Kari - La Quinta, CA 92253
Top tier service by Christopher
Prompt, Professional and friendly. A excellent Hyde’s representative. Give that man a bonus!!
Jim - Palm Springs, CA 92264
Excellent service
Gary - Indio, CA 92201
Christopher was fantastic!
Donald - La Quinta, CA 92253
Great
It seems the whole team is good and conscientious and work to satisfy their customers. Christopher was also great. He changed things up a little and did it his own way. Thanks Christopher.
Stan - Indio, CA 92201
Great service very thorough
Christopher was very professional, thorough, communicative, and very kind
Judy - La Quinta, CA 92253
Hyde always provides excellent service,
Chris was very thorough with all our ACs system and of course answered all my questions.
Laura - La Quinta, CA 92253
Excellent Service
Arrived at time scheduled; so very kind, as he was impressed by the cleanliness of the system and did a complete check-up, outside unit and inside thermostat. Thanks, Hydes for sending the usual great technician. Appreciate that extra attention!!!
Dennis - Palm Desert, CA 92260
Best Service Ever
Christopher was amazing! He explained exactly what he was going to do, checked out our system and reported everything was okay. Very thorough check up!
Lydia - Rancho Mirage, CA 92270
Excellent service great communication
Allan - Cathedral City, CA 92234
Excellent Service. Christopher has serviced our home many times. Knows our home and units here. He is very knowledgeable and has great customer ser
Christopher arrived on time. Performed service and communicated what he was going to do and gave update after
Jim - Indio, CA 92203
Easy service
Kerry - Indio, CA 92203
Seasonal Maintenance
On time, let us know he was on his way, explained what he did and was efficient.
Vincent - Indio, CA 92203
Excellent service
Chris was very thorough, very personable and informative
Keith - Palm Desert, CA 92211
Great Heating Service
Chris from Hydes notified us of his arrival time and performed the maintenance interval on our furnace. He reported the system checks and the results all satisfactory. Always pleased with Chris's profesdionalism.
Ed - Indio, CA 92203

Job Locations

Christopher J.
Christopher J.
Demand call: no cool Upon arrival, client stated warm air was coming from supply vents and breaker had tripped for outdoor unit. Diagnostics revealed the hermetic capacitor was zero. Disconnect box was extremely tight and recommended replacement. In the process of replacing disconnect box, the pull mechanism was completely destroyed. Burnt wires and melted plastic was exposed in the box. Ohmed compressor motor windings and tested to ground to see if compressor motor was internally grounded. Pulled the plug from the compressor and tested to see if terminals were grounded. Also tested condenser fan to see if the fan was grounded. Once everything was assembled, I isolated the fan motor and the breaker did not trip. Then I tested the fan motor and compressor motor together and the breaker did not trip. Synopsis: breaker most likely tripped due to high amperage from failed capacitor and burnt wires at disconnect box. Replacing disconnect box and capacitor was the right diagnostic. Client
La Quinta, CA 92253
La Quinta, CA - Demand call: no cool

Upon arrival, client stated warm air was coming from supply vents and breaker had tripped for outdoor unit. Diagnostics revealed the hermetic capacitor was zero. Disconnect box was extremely tight and recommended replacement. In the process of replacing disconnect box, the pull mechanism was completely destroyed. Burnt wires and melted plastic was exposed in the box. Ohmed compressor motor windings and tested to ground to see if compressor motor was internally grounded. Pulled the plug from the compressor and tested to see if terminals were grounded. Also tested condenser fan to see if the fan was grounded. Once everything was assembled, I isolated the fan motor and the breaker did not trip. Then I tested the fan motor and compressor motor together and the breaker did not trip.

Synopsis: breaker most likely tripped due to high amperage from failed capacitor and burnt wires at disconnect box. Replacing disconnect box and capacitor was the right diagnostic. Client
La Quinta, CA - Demand call: no cool

Upon arrival, client stated warm air was coming from supply vents and breaker had tripped for outdoor unit. Diagnostics revealed the hermetic capacitor was zero. Disconnect box was extremely tight and recommended replacement. In the process of replacing disconnect box, the pull mechanism was completely destroyed. Burnt wires and melted plastic was exposed in the box. Ohmed compressor motor windings and tested to ground to see if compressor motor was internally grounded. Pulled the plug from the compressor and tested to see if terminals were grounded. Also tested condenser fan to see if the fan was grounded. Once everything was assembled, I isolated the fan motor and the breaker did not trip. Then I tested the fan motor and compressor motor together and the breaker did not trip.

Synopsis: breaker most likely tripped due to high amperage from failed capacitor and burnt wires at disconnect box. Replacing disconnect box and capacitor was the right diagnostic. Client
Christopher J.
Christopher J.
Make sure every register was open in every room
Palm Desert, CA 92260
Christopher J.
Christopher J.
Indoor unit safety inspection and maintenance. Equipment executed the sequence of operation in heating with no carbon monoxide detected in the home. Cleared condensate and replaced air filter. Checked static pressure, blower motor amp draw and temperature heat rise. Client renewed club membership – paid via CC. Starbucks.
Palm Springs, CA 92264
Palm Springs, CA - Indoor unit safety inspection and maintenance. Equipment executed the sequence of operation in heating with no carbon monoxide detected in the home. Cleared condensate and replaced air filter. Checked static pressure, blower motor amp draw and temperature heat rise. Client renewed club membership – paid via CC. Starbucks.
Palm Springs, CA - Indoor unit safety inspection and maintenance. Equipment executed the sequence of operation in heating with no carbon monoxide detected in the home. Cleared condensate and replaced air filter. Checked static pressure, blower motor amp draw and temperature heat rise. Client renewed club membership – paid via CC. Starbucks.
Christopher J.
Christopher J.
Indoor unit safety inspection and maintenance (see technician notes for equipment location). Cleared condensate using CO2 and pipe brush. Replaced air filters. Checked blower motor amp draw, static pressure measurements and refrigerant circuit diagnostics. All three systems are functioning according to manufacture specifications. Pre-booked next service for April – Starbucks.
Rancho Mirage, CA 92270
Rancho Mirage, CA - Indoor unit safety inspection and maintenance (see technician notes for equipment location). Cleared condensate using CO2 and pipe brush. Replaced air filters. Checked blower motor amp draw, static pressure measurements and refrigerant circuit diagnostics. All three systems are functioning according to manufacture specifications. Pre-booked next service for April – Starbucks.
Rancho Mirage, CA - Indoor unit safety inspection and maintenance (see technician notes for equipment location). Cleared condensate using CO2 and pipe brush. Replaced air filters. Checked blower motor amp draw, static pressure measurements and refrigerant circuit diagnostics. All three systems are functioning according to manufacture specifications. Pre-booked next service for April – Starbucks.
Christopher J.
Christopher J.
Indoor unit safety inspection and maintenance. Cleared condensate line with a pipe brush and replaced filter. Equipment executed the sequence of operation in heating with no carbon monoxide detected in the home. Checked temperature heat rise, static pressure measurements and blower motor amp draw (see technician notes). Pre-booked next service for April. Starbucks card given.
Rancho Mirage, CA 92270
Rancho Mirage, CA - Indoor unit safety inspection and maintenance. Cleared condensate line with a pipe brush and replaced filter. Equipment executed the sequence of operation in heating with no carbon monoxide detected in the home. Checked temperature heat rise, static pressure measurements and blower motor amp draw (see technician notes). Pre-booked next service for April. Starbucks card given.
Rancho Mirage, CA - Indoor unit safety inspection and maintenance. Cleared condensate line with a pipe brush and replaced filter. Equipment executed the sequence of operation in heating with no carbon monoxide detected in the home. Checked temperature heat rise, static pressure measurements and blower motor amp draw (see technician notes). Pre-booked next service for April. Starbucks card given.
Christopher J.
Christopher J.
Indoor unit safety inspection and maintenance: two gas furnaces. Cleared condensate and replace filters. Equipment executed the sequence of operation in heating with no carbon monoxide detected in the home. Checked blower capacitors and amp draw. Measured static pressure measurements. Thermostat: good. Client renew club membership and both systems are functioning according to manufacture specifications. Paid via C C.
Desert Hot Springs, CA 92240
Desert Hot Springs, CA - Indoor unit safety inspection and maintenance: two gas furnaces. Cleared condensate and replace filters. Equipment executed the sequence of operation in heating with no carbon monoxide detected in the home. Checked blower capacitors and amp draw. Measured static pressure measurements. Thermostat: good. Client renew club membership and both systems are functioning according to manufacture specifications. Paid via C C.
Desert Hot Springs, CA - Indoor unit safety inspection and maintenance: two gas furnaces. Cleared condensate and replace filters. Equipment executed the sequence of operation in heating with no carbon monoxide detected in the home. Checked blower capacitors and amp draw. Measured static pressure measurements. Thermostat: good. Client renew club membership and both systems are functioning according to manufacture specifications. Paid via C C.
Christopher J.
Christopher J.
Indoor unit safety inspection and maintenance for two systems. Cleared condensate drain and replaced filters. Checked static pressure, blower motor amp draw and temperature heat rise. Checked refrigerant circuit diagnostic for heat pump system. Both systems are functioning according to manufacture specifications. Locked home and left keys with security guards.
Palm Springs, CA 92264
Palm Springs, CA - Indoor unit safety inspection and maintenance for two systems. Cleared condensate drain and replaced filters. Checked static pressure, blower motor amp draw and temperature heat rise. Checked refrigerant circuit diagnostic for heat pump system. Both systems are functioning according to manufacture specifications. Locked home and left keys with security guards.
Palm Springs, CA - Indoor unit safety inspection and maintenance for two systems. Cleared condensate drain and replaced filters. Checked static pressure, blower motor amp draw and temperature heat rise. Checked refrigerant circuit diagnostic for heat pump system. Both systems are functioning according to manufacture specifications. Locked home and left keys with security guards.
Christopher J.
Christopher J.
Demand call: no cool Upon arrival, client stated air movement, but wasn't cool air. Air handler, installed in the garage, had the service panel ajar. Circuit board was detached and hanging freely. From the thermostat, demanded a call for cooling. Blower motor initiated moving air. Connector fan/compressor motor was not moving. After a few short moments, compressor and condenser fan was operational. Checked refrigerant temperature and pressure with gauges. Checked compressor amp draw and noticed amperage was increasing beyond RLA. Compressor sounded terrible like it was on the verge of failing. Pulled disconnect to save compressor and disconnect fell apart. Compressor motor does not work and uses R-22 refrigerant. R-22 compressors are no longer available. Set up an appointment with Mike to discuss system replacement. Charged credit card on file for a trip charge and diagnostics fee. Wire nut disconnect box for safety and system is shut off at the service panel. System: no cool at the
La Quinta, CA 92253
La Quinta, CA - Demand call: no cool

Upon arrival, client stated air movement, but wasn't cool air. Air handler, installed in the garage, had the service panel ajar. Circuit board was detached and hanging freely. From the thermostat, demanded a call for cooling. Blower motor initiated moving air. Connector fan/compressor motor was not moving. After a few short moments, compressor and condenser fan was operational. Checked refrigerant temperature and pressure with gauges. Checked compressor amp draw and noticed amperage was increasing beyond RLA. Compressor sounded terrible like it was on the verge of failing. Pulled disconnect to save compressor and disconnect fell apart. Compressor motor does not work and uses R-22 refrigerant. R-22 compressors are no longer available. Set up an appointment with Mike to discuss system replacement. Charged credit card on file for a trip charge and diagnostics fee. Wire nut disconnect box for safety and system is shut off at the service panel.

System: no cool at the
La Quinta, CA - Demand call: no cool

Upon arrival, client stated air movement, but wasn't cool air. Air handler, installed in the garage, had the service panel ajar. Circuit board was detached and hanging freely. From the thermostat, demanded a call for cooling. Blower motor initiated moving air. Connector fan/compressor motor was not moving. After a few short moments, compressor and condenser fan was operational. Checked refrigerant temperature and pressure with gauges. Checked compressor amp draw and noticed amperage was increasing beyond RLA. Compressor sounded terrible like it was on the verge of failing. Pulled disconnect to save compressor and disconnect fell apart. Compressor motor does not work and uses R-22 refrigerant. R-22 compressors are no longer available. Set up an appointment with Mike to discuss system replacement. Charged credit card on file for a trip charge and diagnostics fee. Wire nut disconnect box for safety and system is shut off at the service panel.

System: no cool at the
Christopher J.
Christopher J.
Indoor unit safety inspection and maintenance. Equipment executed the sequence of operation in heating with no carbon monoxide detected in the home. Checked static pressure, blower motor amp draw and temperature heat rise. Replaced filter. Condensate drain pump. Pre-booked next service for April. System is functioning according to manufacture specifications.
Rancho Mirage, CA 92270
Rancho Mirage, CA - Indoor unit safety inspection and maintenance. Equipment executed the sequence of operation in heating with no carbon monoxide detected in the home. Checked static pressure, blower motor amp draw and temperature heat rise. Replaced filter. Condensate drain pump. Pre-booked next service for April. System is functioning according to manufacture specifications.
Rancho Mirage, CA - Indoor unit safety inspection and maintenance. Equipment executed the sequence of operation in heating with no carbon monoxide detected in the home. Checked static pressure, blower motor amp draw and temperature heat rise. Replaced filter. Condensate drain pump. Pre-booked next service for April. System is functioning according to manufacture specifications.
Christopher J.
Christopher J.
Indoor unit safety inspection and maintenance. Removed loose insulation, cleared condensate drain and replaced filter. Checked static pressures, refrigerant circuit diagnostics and electric blower motor amp draw. Thermostat: OK. System is now functioning according to manufacture specifications.
La Quinta, CA 92253
La Quinta, CA - Indoor unit safety inspection and maintenance. Removed loose insulation, cleared condensate drain and replaced filter. Checked static pressures, refrigerant circuit diagnostics and electric blower motor amp draw. Thermostat: OK. System is now functioning according to manufacture specifications.
La Quinta, CA - Indoor unit safety inspection and maintenance. Removed loose insulation, cleared condensate drain and replaced filter. Checked static pressures, refrigerant circuit diagnostics and electric blower motor amp draw. Thermostat: OK. System is now functioning according to manufacture specifications.
Christopher J.
Christopher J.
Indoor unit safety inspection and maintenance. Checked refrigerant circuit diagnostics, blower motor amp draw and static pressure measurements. Cleared condensate, cleaned mechanical platform, and replace filters. Courtesy maintenance on garage/casita mini splits. System is functioning according to manufacture specifications.
La Quinta, CA 92253
La Quinta, CA - Indoor unit safety inspection and maintenance. Checked refrigerant circuit diagnostics, blower motor amp draw and static pressure measurements. Cleared condensate, cleaned mechanical platform, and replace filters. Courtesy maintenance on garage/casita mini splits. System is functioning according to manufacture specifications.
La Quinta, CA - Indoor unit safety inspection and maintenance. Checked refrigerant circuit diagnostics, blower motor amp draw and static pressure measurements. Cleared condensate, cleaned mechanical platform, and replace filters. Courtesy maintenance on garage/casita mini splits. System is functioning according to manufacture specifications.
Christopher J.
Christopher J.
Indoor unit safety inspection and maintenance. Cleared condensate, replaced filter and cleaned mechanical platform. POV installed in the attic – garage access. Checked static pressure readings, blower motor amp draw and refrigerant circuit diagnostics. Thermostat: good. System is currently functioning according to manufacture specifications.
Indio, CA 92201
Indio, CA - Indoor unit safety inspection and maintenance. Cleared condensate, replaced filter and cleaned mechanical platform. POV installed in the attic – garage access. Checked static pressure readings, blower motor amp draw and refrigerant circuit diagnostics. Thermostat: good. System is currently functioning according to manufacture specifications.
Indio, CA - Indoor unit safety inspection and maintenance. Cleared condensate, replaced filter and cleaned mechanical platform. POV installed in the attic – garage access. Checked static pressure readings, blower motor amp draw and refrigerant circuit diagnostics. Thermostat: good. System is currently functioning according to manufacture specifications.
Christopher J.
Christopher J.
Per Janelle discount to $400 and (4) equal payments are approved Cleaned evaporative coil. Charged credit card on file.
Palm Desert, CA 92211
Palm Desert, CA - Per Janelle discount to $400 and (4) equal payments are approved 
Cleaned evaporative coil. Charged credit card on file.
Christopher J.
Christopher J.
Indoor unit safety inspection and maintenance. Installation location of equipment - noted in (technician notes). Checked refrigerant circuit diagnostics, blower motor amp draw and static pressure readings. Cleared condensate drain, clean mechanical platform and replace filters. Thermostat – good. All systems checked OK and are functioning according to manufacture specifications. Community staff to lock and secure home.
La Quinta, CA 92253
La Quinta, CA - Indoor unit safety inspection and maintenance. Installation location of equipment - noted in (technician notes). Checked refrigerant circuit diagnostics, blower motor amp draw and static pressure readings. Cleared condensate drain, clean mechanical platform and replace filters. Thermostat – good. All systems checked OK and are functioning according to manufacture specifications. Community staff to lock and secure home.
La Quinta, CA - Indoor unit safety inspection and maintenance. Installation location of equipment - noted in (technician notes). Checked refrigerant circuit diagnostics, blower motor amp draw and static pressure readings. Cleared condensate drain, clean mechanical platform and replace filters. Thermostat – good. All systems checked OK and are functioning according to manufacture specifications. Community staff to lock and secure home.
Christopher J.
Christopher J.
Indoor unit safety inspection and maintenance. Client was having issues with noises coming from bedroom supply. Noise is due most likely to turbulence when system kicks into second stage cooling. Checked static pressure measurements, refrigerant circuit diagnostics and blower motor amp draw. Replaced filter and cleared condensate drain line. Pre-booked next service for the month of April. System is currently servicing the home at the time of maintenance.
Palm Desert, CA 92211
Palm Desert, CA - Indoor unit safety inspection and maintenance. Client was having issues with noises coming from bedroom supply. Noise is due most likely to turbulence when system kicks into second stage cooling. Checked static pressure measurements, refrigerant circuit diagnostics and blower motor amp draw. Replaced filter and cleared condensate drain line. Pre-booked next service for the month of April. System is currently servicing the home at the time of maintenance.
Palm Desert, CA - Indoor unit safety inspection and maintenance. Client was having issues with noises coming from bedroom supply. Noise is due most likely to turbulence when system kicks into second stage cooling. Checked static pressure measurements, refrigerant circuit diagnostics and blower motor amp draw. Replaced filter and cleared condensate drain line. Pre-booked next service for the month of April. System is currently servicing the home at the time of maintenance.
Christopher J.
Christopher J.
Indoor unit safety inspection and maintenance. After checking refrigerant temperature and pressure, found system to be low on refrigerant. Noticed oil and moisture on low side vapor line. I would suspect the Schrader valve to be faulty, leaking refrigerant from the port, so I took the liberty of replacing the Schrader valve with a new one. Charged system with 2 pounds of refrigerant to restore proper subcool temperatures. Checked running/starting capacitors and electrical motors. Washed air filter. Confirmed TXV metering device. Power shut off was through the service panel. Installed Jones valve and cleared primary condensate drain line. Cleaned air handler platform. System is currently servicing the home at the time of maintenance.
Cathedral City, CA 92234
Cathedral City, CA - Indoor unit safety inspection and maintenance. After checking refrigerant temperature and pressure, found system to be low on refrigerant. Noticed oil and moisture on low side vapor line. I would suspect the Schrader valve to be faulty, leaking refrigerant from the port, so I took the liberty of replacing the Schrader valve with a new one. Charged system with 2 pounds of refrigerant to restore proper subcool temperatures. Checked running/starting capacitors and electrical motors. Washed air filter. Confirmed TXV metering device. Power shut off was through the service panel. Installed Jones valve and cleared primary condensate drain line. Cleaned air handler platform. System is currently servicing the home at the time of maintenance.
Cathedral City, CA - Indoor unit safety inspection and maintenance. After checking refrigerant temperature and pressure, found system to be low on refrigerant. Noticed oil and moisture on low side vapor line. I would suspect the Schrader valve to be faulty, leaking refrigerant from the port, so I took the liberty of replacing the Schrader valve with a new one. Charged system with 2 pounds of refrigerant to restore proper subcool temperatures. Checked running/starting capacitors and electrical motors. Washed air filter. Confirmed TXV metering device. Power shut off was through the service panel. Installed Jones valve and cleared primary condensate drain line. Cleaned air handler platform. System is currently servicing the home at the time of maintenance.
Christopher J.
Christopher J.
Mike to send replacement quote via email
La Quinta, CA 92253
La Quinta, CA - Mike to send replacement quote via email
Christopher J.
Christopher J.
Cancellation
La Quinta, CA 92253
Christopher J.
Christopher J.
Indoor unit safety inspection and maintenance. Gas furnace installed in the garage executed the sequence of operation in heating, with no carbon monoxide detected in the home. Replace filter at filter rack. ECM blower motor. Check static pressure and blower motor amp draw with temperature heat rise. Thermostat/disconnect box: good. System is functioning according to manufacturer specifications.
La Quinta, CA 92253
La Quinta, CA - Indoor unit safety inspection and maintenance. Gas furnace installed in the garage executed the sequence of operation in heating, with no carbon monoxide detected in the home. Replace filter at filter rack. ECM blower motor. Check static pressure and blower motor amp draw with temperature heat rise. Thermostat/disconnect box: good. System is functioning according to manufacturer specifications.
La Quinta, CA - Indoor unit safety inspection and maintenance. Gas furnace installed in the garage executed the sequence of operation in heating, with no carbon monoxide detected in the home. Replace filter at filter rack. ECM blower motor. Check static pressure and blower motor amp draw with temperature heat rise. Thermostat/disconnect box: good. System is functioning according to manufacturer specifications.
Christopher J.
Christopher J.
Rebuilt P-trap on primary condensate line. Filled P-trap with water and tested. Drained water from drain pan to reactivate float safety switch. Client paid via C. C.
Indio, CA 92201
Indio, CA - Rebuilt P-trap on primary condensate line. Filled P-trap with water and tested. Drained water from drain pan to reactivate float safety switch. Client paid via C. C.
Indio, CA - Rebuilt P-trap on primary condensate line. Filled P-trap with water and tested. Drained water from drain pan to reactivate float safety switch. Client paid via C. C.
Christopher J.
Christopher J.
Indoor unit safety check and maintenance. Lennox gas furnace located in the attic – master closet access. Upflow gas furnace – installed in the garage. Split heat pump for casita – installed in an outdoor mechanical closet. All filters are installed at the filter rack. Cleared condensate and cleaned mechanical platform. All furnaces executed the sequence of operation in heating with no carbon monoxide detected in the home. Checked static pressure and temperature heat rise. Measured blower motor amp draw and blower capacitors. Checked refrigerant temperature and pressure for heat pump and tested electric motors. Replaced run capacitor for gas furnace installed in the garage – paid via C. C. Thermostat – good. All systems are functioning according to manufacture specifications.
La Quinta, CA 92253
La Quinta, CA - Indoor unit safety check and maintenance. Lennox gas furnace located in the attic – master closet access. Upflow gas furnace – installed in the garage. Split heat pump for casita – installed in an outdoor mechanical closet. All filters are installed at the filter rack. Cleared condensate and cleaned mechanical platform. All furnaces executed the sequence of operation in heating with no carbon monoxide detected in the home. Checked static pressure and temperature heat rise. Measured blower motor amp draw and blower capacitors. Checked refrigerant temperature and pressure for heat pump and tested electric motors. Replaced run capacitor for gas furnace installed in the garage – paid via C. C. Thermostat – good. All systems are functioning according to manufacture specifications.
La Quinta, CA - Indoor unit safety check and maintenance. Lennox gas furnace located in the attic – master closet access. Upflow gas furnace – installed in the garage. Split heat pump for casita – installed in an outdoor mechanical closet. All filters are installed at the filter rack. Cleared condensate and cleaned mechanical platform. All furnaces executed the sequence of operation in heating with no carbon monoxide detected in the home. Checked static pressure and temperature heat rise. Measured blower motor amp draw and blower capacitors. Checked refrigerant temperature and pressure for heat pump and tested electric motors. Replaced run capacitor for gas furnace installed in the garage – paid via C. C. Thermostat – good. All systems are functioning according to manufacture specifications.
Christopher J.
Christopher J.
Maintenance and safety check service on two split heat pumps. Both systems have TAM air handlers located in indoor/outdoor mechanical closets. Cleared condensate lines and replaced filters. Checked refrigerant circuit diagnostics on both units, capacitors and running/starting amperage measurements on all motors. 2 ton casita unit had a bad dual run capacitor. Replaced – paid via check. Client requesting hardcopy mailed to her address. Renewed club membership.
La Quinta, CA 92253
La Quinta, CA - Maintenance and safety check service on two split heat pumps. Both systems have TAM air handlers located in indoor/outdoor mechanical closets. Cleared condensate lines and replaced filters. Checked refrigerant circuit diagnostics on both units, capacitors and running/starting amperage measurements on all motors. 2 ton casita unit had a bad dual run capacitor. Replaced – paid via check. Client requesting hardcopy mailed to her address. Renewed club membership.
La Quinta, CA - Maintenance and safety check service on two split heat pumps. Both systems have TAM air handlers located in indoor/outdoor mechanical closets. Cleared condensate lines and replaced filters. Checked refrigerant circuit diagnostics on both units, capacitors and running/starting amperage measurements on all motors. 2 ton casita unit had a bad dual run capacitor. Replaced – paid via check. Client requesting hardcopy mailed to her address. Renewed club membership.
Christopher J.
Christopher J.
Indoor safety inspection and maintenance. Cleared condensate, replaced filters and cleaned mechanical platform. Checked refrigerant circuit diagnostic, electric motor amp draw and static pressure measurements. Thermostat: good. Client renew club membership. Both systems are functioning according to manufacture specifications.
La Quinta, CA 92253
La Quinta, CA - Indoor safety inspection and maintenance. Cleared condensate, replaced filters and cleaned mechanical platform. Checked refrigerant circuit diagnostic, electric motor amp draw and static pressure measurements.  Thermostat: good. Client renew club membership. Both systems are functioning according to manufacture specifications.
La Quinta, CA - Indoor safety inspection and maintenance. Cleared condensate, replaced filters and cleaned mechanical platform. Checked refrigerant circuit diagnostic, electric motor amp draw and static pressure measurements.  Thermostat: good. Client renew club membership. Both systems are functioning according to manufacture specifications.
Christopher J.
Christopher J.
Indoor unit safety inspection and maintenance service. Confirmed primary line attachment, ensuring no leaks in condensate plumbing. Equipment executed the sequence of operation with no carbon monoxide detected in the home. Measured temperature heat rise.Checked static pressure, blower motor amp draw and measured capacitor. System is functioning according to manufacturer specifications.
Indio, CA 92203
Indio, CA - Indoor unit safety inspection and maintenance service. Confirmed primary line attachment, ensuring no leaks in condensate plumbing. Equipment executed the sequence of operation with no carbon monoxide detected in the home. Measured temperature heat rise.Checked static pressure, blower motor amp draw and measured capacitor. System is functioning according to manufacturer specifications.
Indio, CA - Indoor unit safety inspection and maintenance service. Confirmed primary line attachment, ensuring no leaks in condensate plumbing. Equipment executed the sequence of operation with no carbon monoxide detected in the home. Measured temperature heat rise.Checked static pressure, blower motor amp draw and measured capacitor. System is functioning according to manufacturer specifications.
Christopher J.
Christopher J.
Indoor unit safety inspection and maintenance. Replaced filters. Heating equipment executed the sequence of operation. Checked blower capacitor, motor amp draw and static pressure measurements. No carbon monoxide was detected in the home. Pre-booked outdoor unit service for the month of April. System is functioning according to manufacture specifications.
Indio, CA 92203
Indio, CA - Indoor unit safety inspection and maintenance. Replaced filters. Heating equipment executed the sequence of operation. Checked blower capacitor, motor amp draw and static pressure measurements. No carbon monoxide was detected in the home. Pre-booked outdoor unit service for the month of April. System is functioning according to manufacture specifications.
Indio, CA - Indoor unit safety inspection and maintenance. Replaced filters. Heating equipment executed the sequence of operation. Checked blower capacitor, motor amp draw and static pressure measurements. No carbon monoxide was detected in the home. Pre-booked outdoor unit service for the month of April. System is functioning according to manufacture specifications.